Novec 1230 (FK-5-1-12) suppression cylinders in a Hyderabad data room (illustration)

Novec 1230 Fire Suppression System in Hyderabad

Last updated: 5 November 2026

A Novec 1230 fire suppression system uses FK-5-1-12, a fluoroketone stored as a liquid, to put out fires in closed rooms without residue. Essatech designs and installs a Novec 1230 fire suppression system in Hyderabad within our wider [fire suppression systems](/fire-suppression-system-hyderabad) service.

FK-5-1-12 is the agent most buyers mean when they ask for a Novec 1230 fire suppression system in Hyderabad. It sits in the cylinder as a liquid and turns to gas as it leaves the nozzle. It is a halocarbon, so it shares the compact cylinders and quick discharge of FM200.

What sets it apart is its climate profile. This page covers the agent, the supply position after 3M left the product line and the rooms where it fits. For the wider family of agents, start with our clean agent fire suppression overview.

What FK-5-1-12 is

FK-5-1-12 is a fluoroketone. At room temperature it is a liquid that evaporates easily, which is why a cylinder can hold a large charge in a small space. On discharge it absorbs heat from the flame and stops the burning reaction.

Its global warming potential is about 1 and it breaks down in the atmosphere within days. HFC-227ea, the agent in FM200, has a potential above 3,000. That gap is why sites with a climate policy ask for a Novec 1230 fire suppression system in Hyderabad.

Safety margin for people

The design concentration of FK-5-1-12 sits well below its NOAEL, the highest level at which no harmful effect is seen. That is why it is accepted in rooms where staff work.

A system still carries a pre-discharge alarm, a time delay and an abort switch. People should leave on the first alarm. Our manned area suppression page lists every control.

After the 3M exit

3M stopped making Novec products at the end of 2025 as part of its exit from PFAS chemicals. The agent itself, FK-5-1-12, is still made and sold by other producers under other names.

For a buyer this changes what to ask. Check who supplies the refill agent, and make sure the system listing covers the agent you will actually receive. Existing systems can still be serviced. We confirm the agent source and listing in every proposal.

Novec 1230 compared with FM200

The two systems look alike on site. Pipes, nozzles, detection and control panel are similar, and both discharge in about 10 seconds. The difference lies in the agent. Our FM200 vs Novec 1230 guide goes through it in full.

Point
Global warming potential
FK-5-1-12
About 1
HFC-227ea (FM200)
Above 3,000
Point
Atmospheric life
FK-5-1-12
Days
HFC-227ea (FM200)
Many years
Point
Storage state
FK-5-1-12
Liquid
HFC-227ea (FM200)
Liquefied gas
Point
Regulatory outlook
FK-5-1-12
Not an HFC
HFC-227ea (FM200)
HFCs phased down under Kigali
Point
Typical fit
FK-5-1-12
Sites with a climate policy
HFC-227ea (FM200)
Projects built around an existing FM200 design

Where it suits

FK-5-1-12 suits rooms where equipment, records or samples are costly and cleanup must be minimal.

  • Data rooms and network closets
  • UPS and battery rooms
  • Museums and art stores
  • Document archives and libraries
  • Laboratories and clean rooms

Novec 1230 projects across Hyderabad

Enquiries for a Novec 1230 fire suppression system in Hyderabad come from technology parks in Hitech City, Madhapur and Kokapet. Tenant policies there often ask for low climate impact agents. Hospitals and labs in Jubilee Hills and Secunderabad ask for it for imaging and sample rooms.

Our Gachibowli team surveys the room and plans the cylinder position. Where a room already has FM200, we can advise whether to keep it, service it under an AMC for suppression systems, or plan a change at the next major refit.

For server rooms, the server room fire suppression page explains how detection and release work together.

Areas we serve. Not sure we cover your area? Call the office and ask.

  • Hitech City
  • Madhapur
  • Kokapet
  • Jubilee Hills
  • Secunderabad
  • Gachibowli

Standards and approvals

Design of a Novec 1230 fire suppression system in Hyderabad follows NFPA 2001 and ISO 14520, with detection to NFPA 72. Cylinders need periodic hydrostatic testing as the cylinder rules require. Approvals belong to specific models, so we share the FM or UL listing for the exact model we quote, and match the approval your insurer or consultant specifies.

The Telangana State Disaster Response & Fire Services Department issues the fire NOC and inspects the building. Essatech prepares the drawings and records.

How the work runs

  1. Send drawingsSend the room plan, height and equipment list, along with any insurer or tenant requirement on the agent.
  2. Survey and designWe visit, test the sealing by eye, and size cylinders, pipe runs and nozzle positions for the room volume.
  3. ProposalYou get the design drawings, the agent source and the listing for the model we propose.
  4. InstallationWe fit the cylinders, pipe network, detectors, hooters and release panel, and close up cable gaps.
  5. Test and hand overA door fan test, interlock checks and staff briefing come before we hand over the records.

Brands we supply

Brand
Siemens
How we work with it
We supply and install this brand
Brand
Rotarex
How we work with it
We supply and install this brand
Brand
Safepro
How we work with it
We supply and install this brand

What to send us

  • Room plan with length, width and height
  • Equipment list and any raised floor or false ceiling details
  • Insurer or tenant requirement on the agent
  • Photos of doors, ducts and cable entries

Questions people ask us

What is Novec 1230?

A Novec 1230 fire suppression system in Hyderabad uses the trade name 3M used for FK-5-1-12, a fluoroketone fire extinguishing agent. It is stored as a liquid and discharges as gas into a closed room. It leaves no residue and has a very low global warming potential. Essatech installs systems using this agent in Hyderabad.

Is Novec 1230 still available after 3M stopped making it?

3M ended Novec production at the end of 2025, but FK-5-1-12 is still made and sold by other producers under other names. Existing systems can be serviced. For a new job we confirm the agent source and the system listing before we quote, so refills stay available.

Is a Novec 1230 system safe in a Hyderabad server room?

Yes, when designed to NFPA 2001. The design concentration is below the safety limit, so staff in a Hyderabad server room are not harmed by a normal discharge. The system still has a pre-discharge alarm and delay, and people should leave when it sounds.

How is Novec 1230 different from FM200?

Both are halocarbons with similar cylinders and discharge time. The difference is climate impact. FK-5-1-12 has a global warming potential of about 1, while HFC-227ea sold as FM200 is above 3,000. Many sites choose FK-5-1-12 for that reason, as HFCs are being phased down.

Which rooms in Hyderabad suit Novec 1230 fire suppression?

Rooms with costly equipment or records suit it, such as data rooms, UPS rooms, museums, archives and labs in Hyderabad. Large open volumes may suit an inert gas bank or water mist better. Our engineers settle the choice after a site survey.

Can an existing FM200 room be changed to Novec 1230?

Sometimes. Each agent has its own listed nozzles, flow design and cylinder fill, so pipes and nozzles must be checked and often replaced. A change is not a simple swap of agent. Our engineers review the layout and tell you whether to convert or keep the FM200.

How often is a Novec 1230 system serviced in Hyderabad?

NFPA 2001 calls for agent quantity and pressure checks at least every six months, with a yearly check of the room. Our Hyderabad team can run these on a schedule and repeat the room integrity test when partitions or cable entries change.